Receptacle

Built-in relay and auto-grouping to co-located luminaires make it easy to meet plug-load requirements.

Get Started
OVERVIEW
The Controlled Receptacle meets electrical code-requirements for automatic shut-off of connected loads when the room is vacant. It automatically pairs with co-located luminaire which provide the occupancy/vacancy status of the room. Integral relay and wireless connectivity simplify installation and eliminate the need for manual programming or external control hardware.

Simply install and energize the Controlled Receptacle and allow for an unobstructed line of sight to at least one co-located luminaire. The Controlled Receptacle is automatically paired to co-located Autonomy Sensors. Once paired, it will be automatically shut off when all lights in the same room detect vacancy and turn on anytime at least one luminaire in the room detects occupancy.
DIMENSIONS
LOAD
ConfigurationSingle (one-pole), switched terminal marked 'Controlled'
Voltage
120 VAC single phase
General AC 20 A
Tungsten 12.5 A
LED/CFL 5 A
Resistive 15 A
Inductive 10 A
Motor 1 HP
Total (Both Poles) 20 A
POWER
Input Voltage 120 VAC 50/60 Hz
Input Current 100 mA maximum internal consumption
Switching Mechanism Zero-cross detection
STANDARDS
UL cULus listed 498-SA (coming soon)
FCC Part 15 Class A
WIRELESS
Communication Protocol 2.4GHz Wireless Mesh.
Transmitter Power +8 dBm.
Range 30 meters (100 ft) line of sight.
ENVIRONMENT
Temperature 0ºC - 40ºC (32ºF - 104ºF)  
Humidity0% - 90% (non-condensing)
EnvironmentDry indoor use only
WARRANTY
5 year manufacturer limited liability

Contact us to learn more

We would be happy to arrange a presentation and a demonstration of our technology. Please contact us or book a meeting to get started.